How to Improve the Construction Level of Computer Room Wiring

2022-08-26 16:25:55

The embodiment of the construction technology level of the wiring in the computer room is the embodiment of the construction level of an engineer. The place where the owner usually visits is the computer room, so the wiring construction of the computer room is the top priority. How can we improve the construction level of the wiring in the computer room?


The wiring in the computer room should not be done arbitrarily. The actual wiring of the network cable should be carried out on the site. When the computer room is newly built or rectified, the network cable and optical fiber jumper are not allowed to use the same cable management or cabinet cable management slot, and should be managed separately in their own dedicated cable management device or cabinet. Wiring is carried out in the slot, and the equipment power cord, network cable and optical fiber jumper are not allowed to be intertwined with each other, and should be bundled separately from the network cable and optical fiber jumper. If the network cable is parallel to the strong current line, the network cable and the strong current line should be kept at an appropriate distance. When arranging and bundling the network cable and the optical fiber jumper, the fixed rope is strictly prohibited to be tied too tightly.


Computer room wiring construction level

1. Specification of equipment power cord wiring

1. The UPS power output socket is only used as a special socket for connecting to other power sockets, and should not be connected to any network equipment power cord.


2. When there are multiple equipment cabinets in the equipment room, the equipment power cables must not be connected and wired across the cabinets.


3. The power cords of the equipment should be routed on the back of the cabinet corresponding to the installation location of the equipment. According to the actual arrangement of the equipment, the power cords of the equipment should be bundled on both sides of the back of the cabinet in an orderly manner according to the actual situation. Route the power cables of the equipment in an orderly manner in the cable management slots on both sides of the back of the cabinet, and bundle them accordingly.

OM3 LC LC

Second, the network cable wiring specification

1. When wiring in a single cabinet, the network cable wiring specification

a. When the switch 1 is connected to the frame 1 or the switch 2 is connected to the frame 3, the network cable wiring specification

The first 16 ports of switch 1 should be in one-to-one correspondence with the card slots of frame 1, and the RJ-45 port 1 of switch 1 should be connected to the RJ-45 port of the first card slot from left to right of frame 1. Switch 1 RJ-45 port 2 is connected to the RJ-45 port of the second card slot from left to right in chassis 1, and so on.


When laying out the network cable, the network cable should go out from the RJ-45 port of the switch and extend downward, and pass from the upper side of the special cable manager for network cable wiring to the special cable manager for network cable wiring. Route the network cables of switch ports 1 and 2 into the first distribution slot from left to right of the cable manager, and route the network cables of switch ports 3 and 4 into the second cable management slot from left to right. And so on), and then pass the same network cable through the RJ-45 port on the lower side of the special cable organizer and connect downward to the corresponding card slot of the frame (Note: When laying the network cable for the frame, you should Route the RJ-45 port network cable in the first card slot from left to right of the chassis into the first cable distribution slot from left to right in the cable manager, and route the RJ-45 port network cable in the second card slot from left to right in the chassis It is routed into the second cabling slot from left to right of the cable manager, and so on), switch 2 is connected to frame 3, and the wiring rules are the same.


1. When switch 1 or 2 is connected to frame 2, the network cable wiring specification

The last 8 ports of switch 1 should correspond to the first 8 card slots of frame 2, and the RJ-45 port 17 of switch 1 should be connected to the RJ-45 port of the first card slot from left to right of frame 2. , the RJ-45 port 18 of switch 1 is connected to the RJ-45 port of the second card slot from left to right of frame 2, and so on.


The last 8 ports of switch 2 should be in one-to-one correspondence with the last 8 card slots of frame 2, and the RJ-45 port 17 of switch 2 should be connected to the RJ-45 port of the 9th card slot from left to right of frame 2. , the RJ-45 port 18 of switch 2 is connected to the RJ-45 port of the 10th card slot from left to right on frame 2, and so on.


When laying out the network cable, the network cable should go out from the first or second RJ-45 port of the switch and extend downward, and pass through the special cable manager for network cable wiring from the special cable manager for network cable wiring. Route the network cables of switch ports 1 and 2 into the first distribution slot from left to right of the cable manager, and route the network cables of switch ports 3 and 4 into the second cable management slot from left to right. And so on), and then pass the wiring through the slot on the rear side of the special cable manager for network cable wiring on the left side of the front of the cabinet, and extend up or down along the front side of the cabinet to the position of the special cable manager for network cable wiring in frame 2. (Note: If there are cable management slots on both sides of the front of the cabinet, the network cables should be routed in the cable management slot on the left side of the front of the cabinet), and then route the network cables through the slot on the rear side of the special cable management device for network cable routing in frame 2. In the special cable manager, the special cable manager for network cable wiring of frame 2 passes through the RJ-45 port down to the corresponding card slot of frame 2 (Note: When laying network cables for frame 2, you should Route the network cable of the RJ-45 port of the first card slot from left to right of the chassis into the first cable distribution slot from left to right of the cable manager, and route the RJ-45 port of the second card slot of the chassis from left to right. The network cable is routed into the second cable splitter from left to right in the cable manager, and so on).


2. When switch one is connected to switch two, the network cable wiring specification

The interconnection of network devices should start from the last port of the switch, and perform wiring in the order of port usage from back to front.


When laying out the network cable, the network cable should go out from the RJ-45 port of switch 1 and extend downwards, and pass through the special cable manager for network cable wiring through the special cable manager for network cable wiring. Route the network cables of switch ports 1 and 2 into the first distribution slot from left to right of the cable manager, and route the network cables of switch ports 3 and 4 into the second distribution slot from left to right of the cable manager. And so on), and then pass the wiring through the rear slot of the special cable manager for network cable wiring on the front side of the cabinet, and extend down along the left side of the front end of the cabinet to the position of the special cable manager for network cable wiring of switch two (Note: if If there are cable management slots on both sides of the front end of the cabinet, the network cables should be routed in the cable management slot on the front side of the cabinet), and then pass through the rear slot of the special cable management device for network cable wiring of switch 2 and into the special cable management device for network cable wiring. , and then go through the special cable manager distribution slot for the second network cable wiring of the switch and go up to the RJ-45 port of the switch two.


3. When wiring across cabinets, network cable wiring specifications

When laying network cables across cabinets, the network cables should extend upward from one side of the cabinet and pass through the wiring holes on the same side of the top of the cabinet, and pass through the wiring holes on the top of the cabinet. Wiring left or right on the bridge to the upper end of the top of the corresponding cabinet, and then extends downward from the bridge to the wiring hole on the top side of the corresponding cabinet and enters the corresponding cabinet. Route the cables from the left or right to the top of the corresponding cabinet, and then pass the wiring holes into the corresponding cabinet from the top and upper side of the corresponding cabinet.


4. Network cable wiring length specification

The network cable wiring should be carried out on-site actual wiring according to the first and second items of the network cable wiring rules. The length of the network cable should not be estimated. The length should be 10-20CM greater than the actual wiring length on site as the optimal length, and the length of the network cable wiring should not be greater than the optimal length.


Four, fiber patch cord wiring specification

1. When only a single cabinet is placed in the computer room and there is no 0DF dedicated cabinet, the optical fiber patch cord should be laid out according to the wiring specification. The optical fiber patch cord should go out from the optical fiber port of the photoelectric conversion card in the frame and extend downward, from the optical fiber jumper. The upper branching slot of the special cable manager for wiring and wiring is inserted into the special cable manager for optical fiber patch cords (Note: When arranging optical fiber patch cords for the chassis, the optical fiber in the first card slot from left to right in the chassis should be Route the optical fiber patch cords of the conversion card into the first distribution slot from left to upper right of the cable manager, and route the optical fiber patch cords of the photoelectric conversion card in the second card slot from left to right in the chassis into the cable manager From the left to the upper right side of the second distribution slot, and so on), and then pass through the rear slot hole of the special cable manager for fiber patch cord wiring, and route the wiring to the left side of the front of the cabinet, and extend up along the left side of the front of the cabinet. Routed into the ODF terminal box (Note: If there are cable management slots on both sides of the front of the cabinet, the fiber patch cords should be wired in the cable management slot on the left side of the front of the cabinet), and then enter the corresponding ODF from the ODF terminal box splitter For the terminal disc of the terminal box, if there is redundancy in the length of the fiber patch cord, the redundant part shall be sorted out and placed at the bottom of the cabinet.


2. When there are multiple cabinets or special cabinets with 0DF in the computer room, the wiring specification of optical fiber jumpers

When there are multiple cabinets in the equipment room and there is no 0DF special cabinet, one cabinet should be designated as the 0DF special cabinet. This cabinet cannot install or place any equipment unrelated to the ODF terminal box. The ODF terminal box is only allowed to be installed in the designated Inside the ODF dedicated cabinet.


When laying out optical fiber patch cords, the optical fiber patch cords should exit from the optical fiber port of the photoelectric conversion card in the chassis and extend downwards, and pass through the cable management slot on the upper side of the special cable management device for optical fiber patch cables (Note). : When laying the optical fiber patch cords for the chassis, the optical fiber patch cords of the photoelectric conversion card in the first card slot from left to right in the chassis should be placed in the first distribution slot from the left to the upper right side of the cable organizer. , Route the optical fiber patch cord of the photoelectric conversion card in the second card slot from left to right in the frame into the second split slot from left to upper right of the cable manager, and so on), and then connect the optical fiber patch cord The rear side of the special cable manager for wiring is routed through the cabling at the front of the cabinet near the side of the ODF special cabinet, and extends upward along the front of the cabinet near the side of the ODF special cabinet (Note: If there are cable management grooves on both sides of the front of the cabinet, it should be Route the fiber patch cords in the front end of the cabinet near the cable management slot on the side of the dedicated ODF cabinet), pass through the wiring holes on the same side of the cabinet top, and pass through the top wiring holes of the cabinet. If the equipment room has a bridge, the fiber patch cords should be passed through the top of the cabinet Enter the upper bridge, and route the cables left or right on the bridge to the upper end of the top of the ODF special cabinet, then extend downward from the bridge, and pass the wiring hole on the left side of the top upper end of the ODF special cabinet into the ODF special cabinet. With a bridge frame, the optical fiber patch cords should be routed to the left or right along the top upper end of the cabinet to the left wiring hole on the top upper end of the ODF special cabinet. Wiring from the left side of the ODF special cabinet to the ODF terminal box splitter (Note: If there are cable management slots on both sides of the front of the cabinet, the fiber patch cords should be wired in the cable management slot on the left side of the front of the cabinet), and then enter the corresponding The terminal disc of the ODF terminal box. If there is redundancy in the length of the optical fiber patch cord, the redundant part shall be sorted out and placed in the special ODF cabinet.